| Parameters | C-module | V-module | ||
| Rated voltage | 12 kV | 24 kV | 12 kV | 24 kV |
| Power frequency withstand voltage | 38 kV/1min | 50 kV/1min | 38 kV/1min | 50 kV/1min |
| Impulse withstand voltage | 95 kV | 125 kV | 95 kV | 125 kV |
| Rated current | 630 A | 630 A | 630 A | 630 A |
| Rated short circuit breaking current | 25 kA | 21 kA | ||
| Rated short circuit making current | 63 kA | 53 kA | 63 kA | 53 kA |
| Rated short time withstand current | 25/3 kA/s | 21/3 kA/s | 25/3 kA/s | 21/3 kA/s |
| Mechanical life | Load 5000 times / earthing 5000 times | Circuit breaker 10000 times / Isolating 5000 times / earthing 5000 times | ||
Note: 1) Please consult our company for special parameters.
RSF-12/24 series inflated switchgear shall comply with IEC62271-100, IEC62271-102, IEC62271-103, IEC62271-200, IEC62271-105, IEC62271-1, GB/T11022-1999, GB3906-2006, GB1985-2004, GB16926, GB3804-2004, GB1984-2003, GB3309-89 and other standards.
The intelligent energy management system helps users improve management efficiency and achieve the energy-saving and emission reduction target.