| DESIGN AND CONSTRUCTION REQUIREMENTS | |||
| GENERAL | |||
| RMU type | Outdoor & Indoor | ||
| RMU configuration | 3-Way / 4-Way | ||
| Tee-off | Circuit breaker | ||
| Terminal fastener for ring switch | M16 | ||
| Terminal fastener for C. B | M16/M12 | ||
| RING SWITCH (LBS) | CIRCUIT BREAKER | ||
| Service voltage | 13.8 kV | Service voltage | 13.8 kV |
| Maximum operating voltage | 17.5 kV | Maximum operating voltage | 17.5 kV |
| Rated frequency | 50/60 Hz | Rated frequency | 50/60 Hz |
| Rated current | 630/400 A | Rated current | 200 A |
| Short circuit withstand current, 1 sec | 21 kA | Rated short circuit level, 1 sec | 21 kA |
| Rated making current (peak) | 54.6 kA | Rated making current | 54.6 kA |
| Rated making current of earthing switch (peak) | 54.6 kA | Re-striking voltage ratio | 1.4 |
| Impulse withstand voltage | 110 kV | Duty cycle | O-t1-CO-t2-CO |
| Power frequency withstand voltage, 1 min. (Ref. 01-SDMS-01) | 45 kV rms | Making time | ms |
| Internal arc fault withstand current for 1 sec | 21 kA | Opening time | ms |
| Arc duration | ms | ||
| Total breaking time | ms | ||
| Operating mechanism | Spring charged | ||